Data Center Cooling Valves
RANGER-FZV supplies hygienic-design valves for direct-to-chip and other data center liquid cooling systems: ball, butterfly and check valves, mini ball valves and strainers with clamp or orbital-weld ends. Bodies are forged and machined from bar stock, wetted metal parts are available in 316L stainless steel, and flow passages are polished, degreased and cleaned. Every valve is shell and seat tested before dispatch, with bubble-tight seats.
Configurations

Three-Piece High-Platform Ball Valves
Full-bore, three-piece ball valves for CDU inlet and outlet isolation and for manifold isolation. With clamp ends the body can be removed from the line by releasing the clamps, without cutting welds.
View full details
Two-Piece Ball Valves
Compact, full-bore, two-piece ball valves for rack branch isolation and for row and branch manifolds.
View full details
Butterfly Valves
Two-piece split-body butterfly valves for larger supply and return headers, where pressure drop is less critical than on branch and rack isolation.
View full details
Check Valves
Spring-loaded poppet check valves for pump discharge, with a low cracking pressure that can be specified at order.
View full details
Mini Ball Valves
One-piece, manually operated ball valves for vents, drains and sample points. Threaded ends should be sealed with pure virgin PTFE tape, not liquid thread sealant.
View full details
Strainers
Strainers upstream of the CDU and racks to protect cold plates and downstream equipment from particles, with low pressure loss.
View full detailsApplicable Standards
- ASME BPE
- GB/T 12237
- GB/T 26480
- ISO 5208
- ISO 5211